CS-01
Flat twin-and-earth clipped direct — 21 A radial on a 25 A Type B breaker, 25 m
Inputs
- Design current Ib = 21 A, single-phase 230 V
- 70 °C thermoplastic flat twin-and-earth, copper
- Reference Method C (clipped direct), 25 m, ambient 30 °C, single circuit
- Protective device In = 25 A (Type B circuit-breaker)
| Quantity | Expected | Source | MEPCalc | Δ | Tolerance | Result |
|---|---|---|---|---|---|---|
Selected conductor size 1.5 mm² carries 20 A < 25 A; 2.5 mm² carries 27 A ≥ 25 A | 2.5mm² | BS 7671:2018+A2:2022 Table 4D5, column 8, printed p456 | 2.5mm² | 0.00 % | exact | Pass |
Tabulated current-carrying capacity, It | 27A | BS 7671:2018+A2:2022 Table 4D5, column 8 (2.5 mm²), printed p456 | 27A | 0.00 % | exact | Pass |
Tabulated voltage drop | 18mV/A/m | BS 7671:2018+A2:2022 Table 4D5, column 9 (2.5 mm²), printed p456 | 18mV/A/m | 0.00 % | exact | Pass |
Voltage drop 18 mV/A/m × 21 A × 25 m ÷ 1000 = 9.45 V | 9.45V | BS 7671:2018+A2:2022 Appendix 4 section 6, printed p429 | 9.45V | 0.00 % | ±2 % | Pass |
Voltage-drop limit 5 % of 230 V = 11.5 V | 11.5V | BS 7671:2018+A2:2022 Table 4Ab row (i), other uses, printed p430 | 11.5V | 0.00 % | exact | Pass |