BS 7671 cable-sizing verification

Fixed worked examples run through MEPCalc's cable-sizing and circuit-design calculations, compared line by line with the values printed in BS 7671:2018+A4:2026 and the IET On-Site Guide.

Result
65 of 65 checks pass
Cases
16 worked examples
Version / published
v1.4 · 2026-09-28
Engine fingerprint
c3b94d233cf2

Why we publish this

No formal certification scheme covers BS 7671 cable sizing. CIBSE TM33 tests building-services thermal software; nothing equivalent exists for the IET wiring regulations. So we publish our own evidence: a fixed set of worked examples, each with its expected value cited to the table, regulation and printed page it comes from, run through the same calculations our users run.

What these calculations do not model

Appendix 4 Equation 1 divides the device rating by its rating factors. The calculations apply ambient temperature, soil thermal resistivity, thermal insulation, the buried-cable factor and the depth-of-laying factor (Cd, Table 4B4, added by A4:2026); grouping comes from Table 4C1, or from Tables 4C2 and 4C3 for buried groups. Every buried case above is at the 0.7 m reference depth, where Cd is 1.00. One factor is deliberately not applied:

  • Semi-enclosed fuse to BS 3036 (Cf = 0.725) — the factor is implemented but no BS 3036 device can be selected, so it is 1.00 on every case above. A circuit protected by one is outside what these calculations cover.

How to read the tables

  • Expected is the value printed in the standard, or a hand calculation from printed values. The working is shown under each quantity.
  • Tolerance is exact for tabulated values and selected sizes, and ±2 % for calculated quantities such as voltage drop, earth-fault loop impedance and adiabatic conductor size.
  • Every check re-runs automatically whenever the calculation code changes, and this page is regenerated from those results. The engine fingerprint above identifies the calculation code the results came from.

Sources

  • BS 7671:2018+A4:2026
  • IET On-Site Guide 9th ed (2026)

Printed page numbers refer to the editions above.

Worked examples

CS-01

Flat twin-and-earth clipped direct — 21 A radial on a 25 A Type B breaker, 25 m

Inputs

  • Design current Ib = 21 A, single-phase 230 V
  • 70 °C thermoplastic flat twin-and-earth, copper
  • Reference Method C (clipped direct), 25 m, ambient 30 °C, single circuit
  • Protective device In = 25 A (Type B circuit-breaker)
Checks for case CS-01
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
1.5 mm² carries 20 A < 25 A; 2.5 mm² carries 27 A ≥ 25 A
2.5mm²
BS 7671:2018+A4:2026
Table 4D5, column 8, printed p484
2.5mm²0.00 %exactPass
Tabulated current-carrying capacity, It
27A
BS 7671:2018+A4:2026
Table 4D5, column 8 (2.5 mm²), printed p484
27A0.00 %exactPass
Tabulated voltage drop
18mV/A/m
BS 7671:2018+A4:2026
Table 4D5, column 9 (2.5 mm²), printed p484
18mV/A/m0.00 %exactPass
Voltage drop
18 mV/A/m × 21 A × 25 m ÷ 1000 = 9.45 V
9.45V
BS 7671:2018+A4:2026
Appendix 4 section 6, printed p457
9.45V0.00 %±2 %Pass
Voltage-drop limit
5 % of 230 V = 11.5 V
11.5V
BS 7671:2018+A4:2026
Table 4Ab row a, other uses, printed p458
11.5V0.00 %exactPass

CS-02

Two-core 70 °C thermoplastic clipped direct — 40 A on a 40 A breaker, 10 m

Inputs

  • Design current Ib = 40 A, single-phase 230 V
  • Multicore 70 °C thermoplastic, non-armoured, copper (two-core)
  • Reference Method C (clipped direct), 10 m, ambient 30 °C, single circuit
  • Protective device In = 40 A
Checks for case CS-02
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
4 mm² carries 36 A < 40 A; 6 mm² carries 46 A ≥ 40 A
6mm²
BS 7671:2018+A4:2026
Table 4D2A, column 6, printed p478
6mm²0.00 %exactPass
Tabulated current-carrying capacity, It
46A
BS 7671:2018+A4:2026
Table 4D2A, column 6 (6 mm²), printed p478
46A0.00 %exactPass
Tabulated voltage drop
7.3mV/A/m
BS 7671:2018+A4:2026
Table 4D2B, column 3 (6 mm²), printed p479
7.3mV/A/m0.00 %exactPass
Voltage drop
7.3 mV/A/m × 40 A × 10 m ÷ 1000 = 2.92 V
2.92V
BS 7671:2018+A4:2026
Appendix 4 section 6, printed p457
2.92V0.00 %±2 %Pass

CS-03

Four-core 90 °C thermosetting SWA on perforated tray — 90 A three-phase on a 100 A device, 20 m

Inputs

  • Design current Ib = 90 A, three-phase 400 V
  • Multicore armoured 90 °C thermosetting, copper (three- or four-core)
  • Reference Method E (perforated cable tray), 20 m, ambient 30 °C, single circuit
  • Protective device In = 100 A
Checks for case CS-03
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
16 mm² carries 99 A < 100 A; 25 mm² carries 131 A ≥ 100 A
25mm²
BS 7671:2018+A4:2026
Table 4E4A, column 5, printed p492
25mm²0.00 %exactPass
Tabulated current-carrying capacity, It
131A
BS 7671:2018+A4:2026
Table 4E4A, column 5 (25 mm²), printed p492
131A0.00 %exactPass
Tabulated voltage drop
1.65mV/A/m
BS 7671:2018+A4:2026
Table 4E4B, column 4, z (25 mm²), printed p493
1.65mV/A/m0.00 %exactPass
Voltage drop
1.65 mV/A/m × 90 A × 20 m ÷ 1000 = 2.97 V
2.97V
BS 7671:2018+A4:2026
Appendix 4 section 6, printed p457
2.97V0.00 %±2 %Pass
Voltage-drop limit
5 % of 400 V = 20 V
20V
BS 7671:2018+A4:2026
Table 4Ab row a, other uses, printed p458
20V0.00 %exactPass

CS-04

Ambient 40 °C — 20 A two-core 70 °C thermoplastic clipped direct on a 20 A device, 10 m

Inputs

  • Design current Ib = 20 A, single-phase 230 V
  • Multicore 70 °C thermoplastic, non-armoured, copper (two-core)
  • Reference Method C (clipped direct), 10 m, ambient 40 °C, single circuit
  • Protective device In = 20 A
Checks for case CS-04
QuantityExpectedSourceMEPCalcΔToleranceResult
Ambient-temperature rating factor, Ca
0.87
BS 7671:2018+A4:2026
Table 4B1, 70 °C thermoplastic at 40 °C, printed p469
0.870.00 %exactPass
Required tabulated capacity, In ÷ (Ca·Cg·Cs·Ci·Cf·Cc)
In ÷ Ca = 20 ÷ 0.87 = 22.99 A (Ib = In on this circuit)
22.99A
BS 7671:2018+A4:2026
Appendix 4 section 5.1.1, Equation 1, printed p453
22.99A0.00 %±2 %Pass
Selected conductor size
1.5 mm² carries 19.5 A < 22.99 A; 2.5 mm² carries 27 A
2.5mm²
BS 7671:2018+A4:2026
Table 4D2A, column 6, printed p478
2.5mm²0.00 %exactPass
Tabulated current-carrying capacity, It
27A
BS 7671:2018+A4:2026
Table 4D2A, column 6 (2.5 mm²), printed p478
27A0.00 %exactPass

CS-05

Three circuits bunched — 20 A two-core 70 °C thermoplastic clipped direct on a 20 A device, 10 m

Inputs

  • Design current Ib = 20 A, single-phase 230 V
  • Multicore 70 °C thermoplastic, non-armoured, copper (two-core)
  • Reference Method C (clipped direct), 10 m, ambient 30 °C, three circuits bunched
  • Protective device In = 20 A
Checks for case CS-05
QuantityExpectedSourceMEPCalcΔToleranceResult
Grouping rating factor, Cg
0.7
BS 7671:2018+A4:2026
Table 4C1, item 1, three circuits, printed p471
0.70.00 %exactPass
Required tabulated capacity, In ÷ (Ca·Cg·Cs·Ci·Cf·Cc)
In ÷ Cg = 20 ÷ 0.70 = 28.57 A (Ib = In on this circuit)
28.57A
BS 7671:2018+A4:2026
Appendix 4 section 5.1.2, Equation 2, printed p453
28.57A0.00 %±2 %Pass
Selected conductor size
2.5 mm² carries 27 A < 28.57 A; 4 mm² carries 36 A
4mm²
BS 7671:2018+A4:2026
Table 4D2A, column 6, printed p478
4mm²0.00 %exactPass
Tabulated current-carrying capacity, It
36A
BS 7671:2018+A4:2026
Table 4D2A, column 6 (4 mm²), printed p478
36A0.00 %exactPass

CS-06

Buried direct in soil of 1.0 K·m/W at 25 °C — 32 A two-core 70 °C thermoplastic SWA on a 32 A device

Inputs

  • Design current Ib = 32 A, single-phase 230 V
  • Multicore armoured 70 °C thermoplastic, copper (two-core)
  • Reference Method D (buried direct), 30 m, soil thermal resistivity 1.0 K·m/W, ground 25 °C
  • Protective device In = 32 A
Checks for case CS-06
QuantityExpectedSourceMEPCalcΔToleranceResult
Soil thermal-resistivity rating factor, Cs
1.5
BS 7671:2018+A4:2026
Table 4B3, direct buried cables at 1.0 K·m/W, printed p470
1.50.00 %exactPass
Ambient-temperature rating factor, Ca
0.95
BS 7671:2018+A4:2026
Table 4B2, 70 °C thermoplastic at 25 °C ground, printed p469
0.950.00 %exactPass
Buried-cable rating factor, Cc
Cc = 0.9 for cables in a duct in the ground or buried direct
0.9
BS 7671:2018+A4:2026
Appendix 4 section 5.1.1, Equation 1 note (b), printed p453
0.90.00 %exactPass
Required tabulated capacity, In ÷ (Ca·Cg·Cs·Ci·Cf·Cc)
In ÷ (Ca × Cs × Cc) = 32 ÷ (0.95 × 1.50 × 0.9) = 24.95 A (Ib = In on this circuit)
24.95A
BS 7671:2018+A4:2026
Appendix 4 section 5.1.1, Equation 1, printed p453
24.95A0.00 %±2 %Pass

CS-07

500 mm run in thermal insulation — 20 A two-core 70 °C thermoplastic on a 20 A device, 10 m

Inputs

  • Design current Ib = 20 A, single-phase 230 V
  • Multicore 70 °C thermoplastic, non-armoured, copper (two-core)
  • Reference Method C (clipped direct), 10 m, ambient 30 °C, 500 mm totally surrounded by thermal insulation
  • Protective device In = 20 A
Checks for case CS-07
QuantityExpectedSourceMEPCalcΔToleranceResult
Thermal-insulation rating factor, Ci
0.5
BS 7671:2018+A4:2026
Appendix 4 section 2.6, length in insulation ≥ 500 mm (conductors up to 10 mm²), printed p451
0.50.00 %exactPass
Required tabulated capacity, In ÷ (Ca·Cg·Cs·Ci·Cf·Cc)
In ÷ Ci = 20 ÷ 0.50 = 40 A (Ib = In on this circuit)
40A
BS 7671:2018+A4:2026
Appendix 4 section 5.1.1, Equation 1, printed p453
40A0.00 %±2 %Pass
Selected conductor size
4 mm² carries 36 A < 40 A; 6 mm² carries 46 A
6mm²
BS 7671:2018+A4:2026
Table 4D2A, column 6, printed p478
6mm²0.00 %exactPass
Tabulated current-carrying capacity, It
46A
BS 7671:2018+A4:2026
Table 4D2A, column 6 (6 mm²), printed p478
46A0.00 %exactPass

CS-08

Four-core 70 °C thermoplastic clipped direct — 50 A three-phase on a 50 A device, 40 m

Inputs

  • Design current Ib = 50 A, three-phase 400 V
  • Multicore 70 °C thermoplastic, non-armoured, copper (three- or four-core)
  • Reference Method C (clipped direct), 40 m, ambient 30 °C, single circuit
  • Protective device In = 50 A
Checks for case CS-08
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
6 mm² carries 41 A < 50 A; 10 mm² carries 57 A
10mm²
BS 7671:2018+A4:2026
Table 4D2A, column 7, printed p478
10mm²0.00 %exactPass
Tabulated current-carrying capacity, It
57A
BS 7671:2018+A4:2026
Table 4D2A, column 7 (10 mm²), printed p478
57A0.00 %exactPass
Tabulated voltage drop
3.8mV/A/m
BS 7671:2018+A4:2026
Table 4D2B, column 4 (10 mm²), printed p479
3.8mV/A/m0.00 %exactPass
Voltage drop
3.8 mV/A/m × 50 A × 40 m ÷ 1000 = 7.6 V
7.6V
BS 7671:2018+A4:2026
Appendix 4 section 6, printed p457
7.6V0.00 %±2 %Pass
Voltage-drop limit
5 % of 400 V = 20 V
20V
BS 7671:2018+A4:2026
Table 4Ab row a, other uses, printed p458
20V0.00 %exactPass

CS-09

Lighting circuit — 5 A on a 6 A Type B breaker, 1.0 mm² flat twin-and-earth clipped direct, 30 m

Inputs

  • Design current Ib = 5 A (the assumed load for a 6 A lighting circuit), single-phase 230 V
  • 70 °C thermoplastic flat twin-and-earth, copper
  • Reference Method C (clipped direct), 30 m, ambient 30 °C, single circuit
  • Protective device In = 6 A (Type B circuit-breaker); lighting voltage-drop limit

The 5 A load for a 6 A lighting circuit is the IET On-Site Guide Table 7.1(i) assumption, printed p84.

Checks for case CS-09
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
1.0 mm² carries 16 A ≥ 6 A
1mm²
BS 7671:2018+A4:2026
Table 4D5, column 8, printed p484
1mm²0.00 %exactPass
Tabulated voltage drop
44mV/A/m
BS 7671:2018+A4:2026
Table 4D5, column 9 (1.0 mm²), printed p484
44mV/A/m0.00 %exactPass
Voltage drop
44 mV/A/m × 5 A × 30 m ÷ 1000 = 6.6 V
6.6V
BS 7671:2018+A4:2026
Appendix 4 section 6, printed p457
6.6V0.00 %±2 %Pass
Voltage-drop limit
3 % of 230 V = 6.9 V
6.9V
BS 7671:2018+A4:2026
Table 4Ab row a, lighting, printed p458
6.9V0.00 %exactPass

CS-10

Ring final circuit (IET On-Site Guide circuit A1) — 32 A Type B, 2.5/1.5 mm² flat twin-and-earth, 60 m loop, TN-C-S

Inputs

  • Ring final circuit, load 26 A (20 A at the far point plus the balance evenly distributed)
  • 70 °C thermoplastic flat twin-and-earth, copper, 2.5 mm² line with 1.5 mm² protective conductor
  • Reference Method C (clipped direct), ring loop 60 m, ambient 30 °C
  • 32 A Type B circuit-breaker, TN-C-S with Ze = 0.35 Ω, 0.4 s disconnection
Checks for case CS-10
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
2.5mm²
IET On-Site Guide 9th ed (2026)
Table H2.1, circuit A1, printed p218
2.5mm²0.00 %exactPass
Voltage drop
26 A over two parallel legs of L/2 is equivalent to L/4 = 15 m: 18 mV/A/m × 26 A × 15 m ÷ 1000 = 7.02 V
7.02V
IET On-Site Guide 9th ed (2026)
Section 7.2.2 load model, printed p96; Table 7.1(i), printed p84
7.02V0.00 %±2 %Pass
Earth-fault loop impedance, Zs
Zs = Ze + (R1 + R2) × L/4 = 0.35 + 19.51 × 1.20 × 15 ÷ 1000 = 0.701 Ω
0.701Ω
IET On-Site Guide 9th ed (2026)
Table I1 (2.5/1.5 mm² = 19.51 mΩ/m), printed p226; Table I3 (×1.20), printed p228
0.7012Ω0.03 %±2 %Pass
Maximum Zs for the device
1.37Ω
BS 7671:2018+A4:2026
Table 41.3(a), Type B 32 A, printed p75
1.37Ω0.00 %exactPass

CS-11

Radial socket circuit (IET On-Site Guide circuit A2) — 32 A Type B, 26 A load, 4/1.5 mm² flat twin-and-earth, 20 m, TN-C-S

Inputs

  • Radial circuit, design current 26 A (the assumed load for a 32 A radial), single-phase 230 V
  • 70 °C thermoplastic flat twin-and-earth, copper
  • Reference Method C (clipped direct), 20 m, ambient 30 °C
  • 32 A Type B circuit-breaker, TN-C-S with Ze = 0.35 Ω, 0.4 s disconnection

The 26 A load for a 32 A radial is the IET On-Site Guide Table 7.1(i) assumption, printed p84.

Checks for case CS-11
QuantityExpectedSourceMEPCalcΔToleranceResult
Selected conductor size
BS 7671 Table 4D5 column 8: 2.5 mm² carries 27 A < 32 A; 4 mm² carries 37 A
4mm²
IET On-Site Guide 9th ed (2026)
Table H2.1, circuit A2, printed p218
4mm²0.00 %exactPass
Voltage drop
11 mV/A/m × 26 A × 20 m ÷ 1000 = 5.72 V
5.72V
BS 7671:2018+A4:2026
Table 4D5, column 9 (4 mm² = 11 mV/A/m), printed p484
5.72V0.00 %±2 %Pass
Earth-fault loop impedance, Zs
Zs = 0.35 + 16.71 × 1.20 × 20 ÷ 1000 = 0.751 Ω
0.751Ω
IET On-Site Guide 9th ed (2026)
Table I1 (4/1.5 mm² = 16.71 mΩ/m), printed p226; Table I3 (×1.20), printed p228
0.751Ω0.00 %±2 %Pass
Maximum Zs for the device
1.37Ω
BS 7671:2018+A4:2026
Table 41.3(a), Type B 32 A, printed p75
1.37Ω0.00 %exactPass

CS-12

The same radial on a 32 A Type C breaker — earth-fault loop impedance governs the size

Inputs

  • Radial circuit, design current 26 A, single-phase 230 V
  • 70 °C thermoplastic flat twin-and-earth, copper
  • Reference Method C (clipped direct), 20 m, ambient 30 °C
  • 32 A Type C circuit-breaker, TN-C-S with Ze = 0.35 Ω, 0.4 s disconnection
Checks for case CS-12
QuantityExpectedSourceMEPCalcΔToleranceResult
Maximum Zs for the device
0.68Ω
BS 7671:2018+A4:2026
Table 41.3(b), Type C 32 A, printed p75
0.68Ω0.00 %exactPass
Selected conductor size
4/1.5 mm² gives Zs = 0.751 Ω > 0.68 Ω, so the next size, 6/2.5 mm², is needed
6mm²
IET On-Site Guide 9th ed (2026)
Table I1 (6/2.5 mm² = 10.49 mΩ/m), printed p226
6mm²0.00 %exactPass
Earth-fault loop impedance, Zs
Zs = 0.35 + 10.49 × 1.20 × 20 ÷ 1000 = 0.602 Ω ≤ 0.68 Ω
0.602Ω
IET On-Site Guide 9th ed (2026)
Table I1 (6/2.5 mm² = 10.49 mΩ/m), printed p226; Table I3 (×1.20), printed p228
0.6018Ω0.03 %±2 %Pass

CS-13

Adiabatic check — copper protective conductor in a 70 °C thermoplastic cable, 6 kA for 0.1 s

Inputs

  • Fault current I = 6000 A, disconnection time t = 0.1 s
  • Copper protective conductor incorporated in a 70 °C thermoplastic cable
  • Installed conductor 25 mm² (used only for the pass/fail comparison)
Checks for case CS-13
QuantityExpectedSourceMEPCalcΔToleranceResult
Adiabatic constant, k
115
BS 7671:2018+A4:2026
Table 54.3, copper, 70 °C thermoplastic, printed p210
1150.00 %exactPass
Minimum conductor size, S
S = √(I²t) ÷ k = √(6000² × 0.1) ÷ 115 = 1897.4 ÷ 115 = 16.5 mm²
16.5mm²
BS 7671:2018+A4:2026
Regulation 543.1.3, printed p209
16.5mm²0.00 %±2 %Pass

CS-14

Adiabatic check — steel wire armour of a 90 °C thermosetting cable as the protective conductor, 10 kA for 0.4 s

Inputs

  • Fault current I = 10 000 A, disconnection time t = 0.4 s
  • Steel wire armour of a 90 °C thermosetting cable used as the protective conductor
  • Installed armour 150 mm² (used only for the pass/fail comparison)
Checks for case CS-14
QuantityExpectedSourceMEPCalcΔToleranceResult
Adiabatic constant, k
46
BS 7671:2018+A4:2026
Table 54.4, steel, 90 °C thermosetting, printed p210
460.00 %exactPass
Minimum conductor size, S
S = √(10 000² × 0.4) ÷ 46 = 6324.6 ÷ 46 = 137.5 mm²
137.5mm²
BS 7671:2018+A4:2026
Regulation 543.1.3, printed p209
137.49mm²0.01 %±2 %Pass

CS-15

The worked example printed in BS 7671 Appendix 4 — 58 A three-phase on a perforated tray with three other circuits, 35 °C

Inputs

  • Design current Ib = 58 A, three-phase 400 V
  • Four-core 90 °C thermosetting insulated cable with steel wire armour, copper
  • Reference Method E (perforated cable tray), single layer, in a group with three other circuits
  • Ambient 35 °C, 20 m
  • Protective device In = 63 A (circuit-breaker to BS EN 60898-1)

This is the only worked example printed in Appendix 4. It appears at section 5.5.2 as the no-harmonics base case before the third-harmonic cases that follow it.

Checks for case CS-15
QuantityExpectedSourceMEPCalcΔToleranceResult
Ambient-temperature rating factor, Ca
0.96
BS 7671:2018+A4:2026
Table 4B1, 90 °C thermosetting at 35 °C, printed p469
0.960.00 %exactPass
Grouping rating factor, Cg
0.77
BS 7671:2018+A4:2026
Table 4C1 item 3, four circuits on a perforated cable tray, printed p471
0.770.00 %exactPass
Selected conductor size
It = In ÷ (Ca × Cg) = 63 ÷ (0.96 × 0.77) = 85.2 A; Table 4E4A column 5: 10 mm² carries 78 A < 85.2 A, 16 mm² carries 99 A ≥ 85.2 A
16mm²
BS 7671:2018+A4:2026
Appendix 4 section 5.5.2 worked example, printed p455
16mm²0.00 %exactPass
Tabulated current-carrying capacity, It
99A
BS 7671:2018+A4:2026
Table 4E4A, column 5 (16 mm²), printed p492
99A0.00 %exactPass

CS-16

Three circuits buried direct and touching, soil 1.0 K·m/W at 25 °C — 32 A two-core 70 °C thermoplastic SWA on a 32 A device

Inputs

  • Design current Ib = 32 A, single-phase 230 V
  • Multicore armoured 70 °C thermoplastic, copper (two-core)
  • Reference Method D (buried direct), 30 m, soil thermal resistivity 1.0 K·m/W, ground 25 °C
  • Group of three circuits, cables touching
  • Protective device In = 32 A

Table 4C1's own Reference Method column reads A to F; buried groups take Tables 4C2 (buried direct) or 4C3 (in buried ducts), printed p472, both keyed by clearance as well as circuit count.

Checks for case CS-16
QuantityExpectedSourceMEPCalcΔToleranceResult
Soil thermal-resistivity rating factor, Cs
1.5
BS 7671:2018+A4:2026
Table 4B3, direct buried cables at 1.0 K·m/W, printed p470
1.50.00 %exactPass
Ambient-temperature rating factor, Ca
0.95
BS 7671:2018+A4:2026
Table 4B2, 70 °C thermoplastic at 25 °C ground, printed p469
0.950.00 %exactPass
Grouping rating factor, Cg
Table 4C1 item 1 (Methods A to F) would give 0.70 — Table 4C2 is the table printed for Reference Method D
0.65
BS 7671:2018+A4:2026
Table 4C2, three circuits, cables touching (nil clearance), printed p472
0.650.00 %exactPass
Buried-cable rating factor, Cc
Cc = 0.9 for cables in a duct in the ground or buried direct
0.9
BS 7671:2018+A4:2026
Appendix 4 section 5.1.1, Equation 1 note (b), printed p453
0.90.00 %exactPass
Required tabulated capacity, In ÷ (Ca·Cg·Cs·Ci·Cf·Cc)
In ÷ (Ca × Cg × Cs × Cc) = 32 ÷ (0.95 × 0.65 × 1.50 × 0.9) = 38.39 A (Ib = In on this circuit); with Table 4C1's 0.70 it would be 35.64 A
38.39A
BS 7671:2018+A4:2026
Appendix 4 section 5.1.2, Equation 2, printed p453
38.39A0.00 %±2 %Pass
Selected conductor size
4 mm² carries 38 A < 38.39 A; 6 mm² carries 48 A ≥ 38.39 A — with Table 4C1's 0.70 the 4 mm² cable (38 A ≥ 35.64 A) would have been selected, one size too small
6mm²
BS 7671:2018+A4:2026
BS 7671:2018+A4:2026 Table 4D4A, column 8 (Reference Method D2, direct in ground), page 482
6mm²0.00 %exactPass
Tabulated current-carrying capacity, It
48A
BS 7671:2018+A4:2026
BS 7671:2018+A4:2026 Table 4D4A, column 8 (6 mm², Reference Method D2), page 482
48A0.00 %exactPass