Verification
Check the working. See the evidence.
- Pages
- 12
- Worked examples
- 127
- Checks
- 374 of 374 pass
Published verification
Choose a calculation to inspect its fixed inputs, cited expected values and measured results. This is our own verification, not independent certification.
Heating, cooling and mixing of moist air against the worked examples printed in ASHRAE Fundamentals 2021 Chapter 1, and the Approved Document L fan power limit.
- Standards cited
- Approved Document L, Volume 2: Buildings other than dwellings, 2026 edition
- ASHRAE Handbook—Fundamentals 2021 (SI), Chapter 1 Psychrometrics
- Worked examples
- 4
- Checks
- 8
- Version / published
- v1.0 · 2026-09-28
- Engine fingerprint
- 4017503a697e
BS 7671 cable sizing
65/65 passConductor selection, rating factors, voltage drop, earth-fault loop impedance and adiabatic conductor size against BS 7671 Appendix 4, Chapter 41, Chapter 54 and the IET On-Site Guide.
- Standards cited
- BS 7671:2018+A4:2026
- IET On-Site Guide 9th ed (2026)
- Worked examples
- 16
- Checks
- 65
- Version / published
- v1.4 · 2026-09-28
- Engine fingerprint
- c3b94d233cf2
Duct fitting losses, circular equivalents, duct insulation, duct friction, duct sizing and louvre sizing against the worked examples and tables printed in CIBSE Guide B2 2016, CIBSE Guide C 2007 and the ASHRAE Handbook—Fundamentals 2021.
- Standards cited
- ASHRAE Handbook—Fundamentals 2021 (SI)
- CIBSE Guide B2 2016, Ventilation and ductwork
- CIBSE Guide C 2007, Reference data
- Worked examples
- 13
- Checks
- 41
- Version / published
- v1.1 · 2026-09-29
- Engine fingerprint
- 8747f047f32c
BS 7671 earthing and fault current
46/46 passEarth-fault loop impedance, the Chapter 41 Zs limits, the Appendix 3 measured-Zs rule, protective-conductor sizing and prospective fault current against BS 7671 Chapters 41 and 54, Appendices 3, 4 and 14 and the IET On-Site Guide.
- Standards cited
- BS 7671:2018+A4:2026
- IET On-Site Guide 9th ed (2026)
- Worked examples
- 16
- Checks
- 46
- Version / published
- v1.1 · 2026-09-28
- Engine fingerprint
- 42b07271a573
Wind and stack pressures, the cross, stack and single-sided flows, the purge and openable areas and the depth limits, against the worked examples, tables and equations printed in CIBSE Guide A 2015, BS EN 16798-7:2017, the ASHRAE Handbook—Fundamentals 2021, ASHRAE 62.1-2022, Approved Document F and CIBSE Guide B2.
- Standards cited
- Approved Document F Volume 1, 2026 edition
- ASHRAE Handbook—Fundamentals 2021 (SI)
- ASHRAE Standard 62.1-2022
- CIBSE Guide B2 2016, Ventilation and ductwork
- CIBSE Guide A 2015, Environmental design
- BS EN 16798-7:2017, Ventilation calculation methods
- Worked examples
- 12
- Checks
- 22
- Version / published
- v1.3 · 2026-09-30
- Engine fingerprint
- 8512625f106b
Solar PV yield to SAP 10.3 and MCS 032
54/54 passAnnual solar radiation from SAP 10.3 Appendix U (Equations U1–U4, Tables U3–U5), annual yield from Equation M1 with the Table M1 overshading factors, the EREC G98 16 A per phase boundary, and the MCS 032:2025 standard estimate (kWp × Kk × SF) with its MGD 003 self-consumption look-up, against the standard's own worked examples.
- Standards cited
- EREC G98 Issue 2 (2025)
- MCS 032:2025 Issue 1.0 (01/01/2025), Solar PV & Battery: Pre-Sale Information and System Performance Estimate Standard
- MCS Irradiance Datasets v2.0 (the kWh/kWp tables MCS 032 §3.1.2 reads)
- SAP 10.3 (13-01-2026), The Government's Standard Assessment Procedure
- Worked examples
- 21
- Checks
- 54
- Version / published
- v1.1 · 2026-09-28
- Engine fingerprint
- bfecad71c34c
Refrigerated-facility loads (Chapter 24), refrigerant line sizing and riser oil return (Chapter 1) and freezing time (Chapter 20) against the worked examples printed in the ASHRAE Handbook—Refrigeration 2022, and the coldroom worked example in the Institute of Refrigeration's Good Practice Guide 150 (2026).
- Standards cited
- ASHRAE Handbook—Refrigeration 2022 (SI)
- Institute of Refrigeration, RACHP Engineering Technicians Section, Good Practice Guide 150: Calculating Heat Loads for Cold Stores (March 2026)
- Worked examples
- 12
- Checks
- 39
- Version / published
- v1.1 · 2026-09-27
- Engine fingerprint
- 750860536b42
The MCS 024:2025 solar heating performance estimate (SAP 2012 Appendix H with the standard's modified inputs: occupancy, daily demand, the modified solar-to-load ratio, EN 12976 collector defaults, the fuel saving by back-up heater) against the standard's printed tables and its Appendix B examples, and the SAP 10.3 Appendix H monthly worksheet against hand-worked examples.
- Standards cited
- MCS 024:2025 Issue 1.0 (01/01/2025), Solar Heating Performance Estimate
- MCS Technical Note: Calculation for Solar Thermal Total Installed Capacity v1.1
- SAP 10.3 (13-01-2026), The Government's Standard Assessment Procedure, Appendix H
- SAP 2012 version 9.92 (October 2013), Appendix H and Table 1b
- Worked examples
- 13
- Checks
- 54
- Version / published
- v1.0 · 2026-09-28
- Engine fingerprint
- df84f8eefac9
Steady-state heat loss, the cyclic-model cooling load and the radiant time series against the worked examples printed in CIBSE Guide A 2015 and the ASHRAE Handbook—Fundamentals 2021.
- Standards cited
- ASHRAE Handbook—Fundamentals 2021 (SI)
- CIBSE Guide A 2015, Environmental design
- Worked examples
- 5
- Checks
- 14
- Version / published
- v1.1 · 2026-09-29
- Engine fingerprint
- bcb2578cc95f
The specific fan power limits the Standalone Fan calculation applies, against Table 5.9 of Approved Document L Volume 2.
- Standards cited
- Approved Document L, Volume 2: Buildings other than dwellings, 2026 edition
- Worked examples
- 3
- Checks
- 6
- Version / published
- v1.0 · 2026-09-28
- Engine fingerprint
- ba5190d7e8d9
Outdoor-air rates, ventilation effectiveness, healthcare air-change rates and specific fan power limits against the printed tables.
- Standards cited
- Approved Document F, Volume 2: Buildings other than dwellings, 2021 edition
- Approved Document L, Volume 2: Buildings other than dwellings, 2026 edition
- ANSI/ASHRAE Standard 62.1-2022, Ventilation and Acceptable Indoor Air Quality
- Addendum j to ANSI/ASHRAE Standard 62.1-2022 (2024), incorporated in 62.1-2025
- CIBSE Guide A 2015, Environmental design
- HTM 03-01 Specialised ventilation for healthcare premises, Part A (2021)
- Worked examples
- 8
- Checks
- 14
- Version / published
- v1.2 · 2026-09-30
- Engine fingerprint
- 7a4198511c4a
Whole dwelling supply and wet-room extract rates against Tables 1.2 and 1.3 of Approved Document F Volume 1.
- Standards cited
- Approved Document F, Volume 1: Dwellings, 2026 edition
- Worked examples
- 4
- Checks
- 11
- Version / published
- v1.0 · 2026-09-28
- Engine fingerprint
- 7a4198511c4a
How we verify
- Fixed worked examples. Each case has fixed inputs and an expected value for every quantity it checks. Nothing is fitted to the engine.
- Every expected value is cited to a printed page. It is either a value read from the standard's own table, or a hand calculation from printed values with the working shown.
- Exact on tabulated values, ±2 % on calculated ones. A table lookup or a selected conductor size must match exactly. A quantity the engine calculates from tabulated inputs passes within ±2 %.
- Re-run in CI on every engine change. The checks run automatically whenever the calculation code changes, and each page is regenerated from those results. A change that moves any result fails the build until the page is regenerated and reviewed.
- Engine fingerprint per page. Each page carries a fingerprint of the calculation code its results came from, so a reader can tell whether the results are current.