Why we publish this
These are the documents the calculation cites. Guide A prints a worked example for the driving pressures and standard formulae for the flows; BS EN 16798-7 and the ASHRAE Handbook print their flow equations and constants; ASHRAE 62.1, Approved Document F and Guide B2 print the tables the compliance checks read. Where a document prints a worked answer it is compared directly; where it prints the method, the method is worked by hand from the printed equation and constants, and the working is shown under each quantity. A tabulated value has to match exactly, and a figure worked from printed inputs has to land within 2 %.
The calculation reports the pressure difference across the building, windward minus leeward, which is what drives the flow, so the print's two facade pressures in Example 4.1 are compared as their difference.
Correction, 29 September 2026
Version 1.0 of this page cited the urban pressure coefficients (+0.2 and −0.25) to Guide A Table 4.A1.1. They are in Table 4.A1.3, the highly sheltered case; the text copy of Guide A the page was built from had lost the reference. The values were right. Separately, the calculation now takes the larger of the wind and stack flows when both act, as Table 4.25(c) prints, where it had added them in quadrature.
Correction, 30 September 2026
Up to version 1.1 the calculation limited a room with a single single-sided opening to 2 times the floor-to-ceiling height, a figure no held print gives. Guide B2 Table 2.5 sets 2.5 times the height for single-sided openings without dividing them by number, so both single-sided strategies now take 2.5 times, and the single opening is compared above.
What is not compared, and why
- The wind-speed correction in Example 4.1. The print first corrects the meteorological 4 m/s at 10 m to the building height and terrain with its equation 4.14 and Table 4.9 (3.87 m/s in open country, 2.35 m/s in an urban setting). The calculation takes the wind speed at the building as an input, so the corrected speeds are given to it and the correction itself is not compared.
- Guide A Table 4.26, openings on one side only. The calculation follows BS EN 16798-7 for single-sided ventilation, compared above, which gives a different flow from Table 4.26's older formulae.
- BS EN 16798-7's cross-ventilation equation (47). It weights the wind term with its own coefficient and half the series area. The calculation uses Guide A's Table 4.25 form for cross flow, compared above.
How to read the tables
- Expected is the value printed in the standard, or a hand calculation from printed values. The working is shown under each quantity.
- Tolerance is exact for tabulated values and selected sizes, and ±2 % for calculated quantities such as the pressure differences, the flows and the opening areas.
- Every check re-runs automatically whenever the calculation code changes, and this page is regenerated from those results. The engine fingerprint above identifies the calculation code the results came from.
Sources
- Approved Document F Volume 1, 2026 edition
- ASHRAE Handbook—Fundamentals 2021 (SI)
- ASHRAE Standard 62.1-2022
- CIBSE Guide B2 2016, Ventilation and ductwork
- CIBSE Guide A 2015, Environmental design
- BS EN 16798-7:2017, Ventilation calculation methods
Printed page numbers refer to the editions above.