Natural ventilation verification against CIBSE Guide A, BS EN 16798-7, ASHRAE and Approved Document F

The 8 m building of Guide A's Figure 4.14, its wind and stack pressures, and the cross and stack flows that Guide A's Table 4.25 formulae give for it, alone and together. Then single-sided airing by BS EN 16798-7, stack flow by the ASHRAE Handbook's Chapter 16, the purge openings of Approved Document F, the minimum openable areas of ASHRAE 62.1 and the depth limits of Guide B2, all run through the same calculation the app uses and compared with the printed figures.

Result
22 of 22 checks pass
Cases
12 worked examples
Version / published
v1.3 · 2026-09-30
Engine fingerprint
8512625f106b

Why we publish this

These are the documents the calculation cites. Guide A prints a worked example for the driving pressures and standard formulae for the flows; BS EN 16798-7 and the ASHRAE Handbook print their flow equations and constants; ASHRAE 62.1, Approved Document F and Guide B2 print the tables the compliance checks read. Where a document prints a worked answer it is compared directly; where it prints the method, the method is worked by hand from the printed equation and constants, and the working is shown under each quantity. A tabulated value has to match exactly, and a figure worked from printed inputs has to land within 2 %.

The calculation reports the pressure difference across the building, windward minus leeward, which is what drives the flow, so the print's two facade pressures in Example 4.1 are compared as their difference.

Correction, 29 September 2026

Version 1.0 of this page cited the urban pressure coefficients (+0.2 and −0.25) to Guide A Table 4.A1.1. They are in Table 4.A1.3, the highly sheltered case; the text copy of Guide A the page was built from had lost the reference. The values were right. Separately, the calculation now takes the larger of the wind and stack flows when both act, as Table 4.25(c) prints, where it had added them in quadrature.

Correction, 30 September 2026

Up to version 1.1 the calculation limited a room with a single single-sided opening to 2 times the floor-to-ceiling height, a figure no held print gives. Guide B2 Table 2.5 sets 2.5 times the height for single-sided openings without dividing them by number, so both single-sided strategies now take 2.5 times, and the single opening is compared above.

What is not compared, and why

  • The wind-speed correction in Example 4.1. The print first corrects the meteorological 4 m/s at 10 m to the building height and terrain with its equation 4.14 and Table 4.9 (3.87 m/s in open country, 2.35 m/s in an urban setting). The calculation takes the wind speed at the building as an input, so the corrected speeds are given to it and the correction itself is not compared.
  • Guide A Table 4.26, openings on one side only. The calculation follows BS EN 16798-7 for single-sided ventilation, compared above, which gives a different flow from Table 4.26's older formulae.
  • BS EN 16798-7's cross-ventilation equation (47). It weights the wind term with its own coefficient and half the series area. The calculation uses Guide A's Table 4.25 form for cross flow, compared above.

How to read the tables

  • Expected is the value printed in the standard, or a hand calculation from printed values. The working is shown under each quantity.
  • Tolerance is exact for tabulated values and selected sizes, and ±2 % for calculated quantities such as the pressure differences, the flows and the opening areas.
  • Every check re-runs automatically whenever the calculation code changes, and this page is regenerated from those results. The engine fingerprint above identifies the calculation code the results came from.

Sources

  • Approved Document F Volume 1, 2026 edition
  • ASHRAE Handbook—Fundamentals 2021 (SI)
  • ASHRAE Standard 62.1-2022
  • CIBSE Guide B2 2016, Ventilation and ductwork
  • CIBSE Guide A 2015, Environmental design
  • BS EN 16798-7:2017, Ventilation calculation methods

Printed page numbers refer to the editions above.

Worked examples

NV-01

Guide A Example 4.1 — wind pressure on the facades of an 8 m building, open country and urban

Inputs

  • Building 8 m high, wind normal to facade 1, outside air at 0 °C
  • Wind speed at building height 3.87 m/s (open country) and 2.35 m/s (urban), the print's corrected speeds
  • Pressure coefficients: facade 1 +0.7 and facade 2 −0.2 in open country (Table 4.A1.1, exposed, p4-33); +0.2 and −0.25 in the urban setting (Table 4.A1.3, highly sheltered, p4-34)
Checks for case NV-01
QuantityExpectedSourceMEPCalcΔToleranceResult
Wind pressure difference, windward to leeward, open country
Table 4.12: facade 1 6.6 Pa, facade 2 −1.9 Pa; difference 8.5 Pa
8.5Pa
CIBSE Guide A 2015, Environmental design
Chapter 4, Example 4.1 (printed p4-21) and Table 4.12 (printed p4-22)
8.406Pa1.11 %±2 %Pass
Wind pressure difference, windward to leeward, urban
Table 4.12: facade 1 0.7 Pa, facade 2 −0.87 Pa; difference 1.57 Pa
1.57Pa
CIBSE Guide A 2015, Environmental design
Chapter 4, Example 4.1 (printed p4-21) and Table 4.12 (printed p4-22)
1.55Pa1.27 %±2 %Pass

NV-02

Guide A Example 4.2 — stack pressure across openings 4 m apart, 20 °C inside and 0 °C outside

Inputs

  • Openings 3 and 4 are 4 m above openings 1 and 2; inside 20 °C, outside 0 °C
Checks for case NV-02
QuantityExpectedSourceMEPCalcΔToleranceResult
Stack pressure difference across the 4 m between openings
Table 4.13: −3.5 Pa at the upper openings relative to the lower (equation 4.17)
3.5Pa
CIBSE Guide A 2015, Environmental design
Chapter 4, Example 4.2 (printed p4-21) and Table 4.13 (printed p4-22)
3.452Pa1.37 %±2 %Pass

NV-03

Guide A Table 4.25(a) — cross ventilation by wind alone

Inputs

  • One 1 m² opening on each facade, no discharge coefficient entered: the CIBSE default Cd 0.61 (Guide A p4-17, sharp-edged opening)
  • Wind 3.87 m/s at building height (Example 4.1, open country); Cp +0.7 windward, −0.2 leeward (Table 4.A1.1)
  • No temperature difference
Checks for case NV-03
QuantityExpectedSourceMEPCalcΔToleranceResult
Wind-driven flow
q = Cd·Aw·vr·(ΔCp)^0.5, 1/Aw² = 1/1² + 1/1² → Aw = 0.7071 m²; 0.61 × 0.7071 × 3.87 × √0.9 = 1.584 m³/s
1.5836m³/s
CIBSE Guide A 2015, Environmental design
Chapter 4, Table 4.25, printed p4-28, with Cd 0.61 from p4-17
1.5836m³/s0.00 %±2 %Pass

NV-04

Guide A Table 4.25(b) — stack ventilation by temperature difference alone

Inputs

  • A 1 m² opening low and a 1 m² opening 4 m higher, CIBSE default Cd 0.61 (p4-17); inside 20 °C, outside 0 °C (Example 4.2)
  • No wind
Checks for case NV-04
QuantityExpectedSourceMEPCalcΔToleranceResult
Stack-driven flow
q = Cd·Ab·(2·Δθ·ha·g / (θ̄ + 273))^0.5 = 0.61 × 0.7071 × (2 × 20 × 4 × 9.81 / 283)^0.5 = 1.016 m³/s
1.0158m³/s
CIBSE Guide A 2015, Environmental design
Chapter 4, Table 4.25, printed p4-28, with Cd 0.61 from p4-17
1.0155m³/s0.03 %±2 %Pass

NV-05

Guide A Table 4.25(c) — wind and temperature difference together: the larger of the two

Inputs

  • The openings and conditions of NV-03 and NV-04 at once: 3.87 m/s wind and 20 K between the openings

Adding the two in quadrature, as the calculator did until September 2026, would give 1.882 m³/s, 19 % above the print.

Checks for case NV-05
QuantityExpectedSourceMEPCalcΔToleranceResult
Wind-driven flow
as NV-03
1.5836m³/s
CIBSE Guide A 2015, Environmental design
Chapter 4, Table 4.25, printed p4-28, with Cd 0.61 from p4-17
1.5836m³/s0.00 %±2 %Pass
Stack-driven flow
as NV-04
1.0158m³/s
CIBSE Guide A 2015, Environmental design
Chapter 4, Table 4.25, printed p4-28, with Cd 0.61 from p4-17
1.0155m³/s0.03 %±2 %Pass
Design flow, the larger of the two
vr/√Δt = 3.87/√20 = 0.87 > 0.26·(Ab/Aw)·(ha/ΔCp)^0.5 = 0.26 × 1 × (4/0.9)^0.5 = 0.55, so qvt = qvw = 1.584 m³/s
1.5836m³/s
CIBSE Guide A 2015, Environmental design
Chapter 4, Table 4.25, printed p4-28, with Cd 0.61 from p4-17
1.5836m³/s0.00 %±2 %Pass

NV-06

BS EN 16798-7 Eq (45) — one window, stack governing

Inputs

  • Single-sided, one opening 1.0 m wide × 1.5 m high (1.5 m²), so h_w;st = 1.5 m (Eq 44)
  • Inside 26 °C, outside 20 °C (the reference temperature, so the Eq (45) density ratio is 1); wind 2 m/s
Checks for case NV-06
QuantityExpectedSourceMEPCalcΔToleranceResult
Airflow through the window
3600 × (1.5/2) × max(0.001 × 2², 0.0035 × 1.5 × 6)^0.5 = 3600 × 0.75 × 0.03150^0.5
479.2m³/h
BS EN 16798-7:2017, Ventilation calculation methods
§6.4.3.5.4.2 Eq (45) with Eq (44) (printed p34) and Table 11 (printed p26)
479.16m³/h0.01 %±2 %Pass

NV-07

BS EN 16798-7 Eq (45) — the same window, wind governing

Inputs

  • As NV-06 with the wind at 6 m/s
Checks for case NV-07
QuantityExpectedSourceMEPCalcΔToleranceResult
Airflow through the window
3600 × 0.75 × max(0.001 × 6², 0.0315)^0.5 = 3600 × 0.75 × 0.036^0.5
512.3m³/h
BS EN 16798-7:2017, Ventilation calculation methods
§6.4.3.5.4.2 Eq (45) with Eq (44) (printed p34) and Table 11 (printed p26)
512.28m³/h0.00 %±2 %Pass

NV-08

BS EN 16798-7 Eqs (44) and (45) — high and low windows on one facade

Inputs

  • Two openings 1.0 m wide × 0.5 m high (0.5 m² each), centres at 1.0 m and 2.5 m
  • Inside 26 °C, outside 20 °C; wind 2 m/s
Checks for case NV-08
QuantityExpectedSourceMEPCalcΔToleranceResult
Airflow through the window
h_w;st = (2.5 + 0.25) − (1.0 − 0.25) = 2.0 m (Eq 44); 3600 × (1.0/2) × max(0.004, 0.0035 × 2.0 × 6)^0.5
368.9m³/h
BS EN 16798-7:2017, Ventilation calculation methods
§6.4.3.5.4.2 Eq (45) with Eq (44) (printed p34) and Table 11 (printed p26)
369m³/h0.03 %±2 %Pass

NV-09

ASHRAE Fundamentals Ch.16 Eq (38) — stack flow through two equal openings

Inputs

  • Two 1 m² openings 4 m apart, ASHRAE design standard, no discharge coefficient entered: the ASHRAE default C_D 0.65 (the unidirectional value in the text after Eq (39))
  • Inside 20 °C, outside 10 °C; no wind

The print divides by the inside temperature; the calculation divides by the mean of inside and outside (Guide A's θ̄), which puts it 0.9 % above the print at this temperature difference.

Checks for case NV-09
QuantityExpectedSourceMEPCalcΔToleranceResult
Stack-driven flow through the two openings
Equal openings put the neutral plane midway, ΔH_NPL = 2 m: 0.65 × 1.0 × (2 × 9.81 × 2 × 10 / 293.15)^0.5
0.752m³/s
ASHRAE Handbook—Fundamentals 2021 (SI)
Chapter 16, Eq (38) and the text after Eq (39), printed p16.14
0.7585m³/s0.86 %±2 %Pass

NV-10

Approved Document F Vol 1 Table 1.4 — purge ventilation openings for a 24 m² room

Inputs

  • Room 6 × 4 m (24 m²); hinged windows opening 45°, then 20°
Checks for case NV-10
QuantityExpectedSourceMEPCalcΔToleranceResult
Purge opening area, openings at 30° or more
1/20 of the floor area for 30° or more: 24 / 20
1.2m²
Approved Document F Volume 1, 2026 edition
Table 1.4, purge ventilation openings (printed p10)
1.2m²0.00 %exactPass
Purge opening area, openings at 15 to 30°
1/10 of the floor area for 15 to 30°: 24 / 10
2.4m²
Approved Document F Volume 1, 2026 edition
Table 1.4, purge ventilation openings (printed p10)
2.4m²0.00 %exactPass

NV-11

ASHRAE 62.1-2022 Tables 6-7 and 6-8 — minimum openable area for a 24 m² office

Inputs

  • Office 6 × 4 m (24 m²), Rp 2.5 L/s·person and Ra 0.3 L/s·m² (Table 6-1)
  • Two 1 m² openings 2 m apart, 10 people: Vbz/Az = (25 + 7.2)/24 = 1.34 L/s·m² → the 2.0 row; Hvs 2 m ≤ 2.5 m, As/Al 1.0 > 0.5
  • One 1 m × 1 m opening, 40 people: Vbz/Az = (100 + 7.2)/24 = 4.47 L/s·m² → the 5.5 row; Hs/Ws 1.0
Checks for case NV-11
QuantityExpectedSourceMEPCalcΔToleranceResult
Minimum openable area, Table 6-8
2.6% of floor
ASHRAE Standard 62.1-2022
Table 6-8 (printed p28), with Table 6-1 office rates (printed p19)
2.6% of floor0.00 %exactPass
Minimum openable area, two openings 2 m apart
2.6 % × 24 m²
0.624m²
ASHRAE Standard 62.1-2022
Table 6-8 (printed p28), with Table 6-1 office rates (printed p19)
0.624m²0.00 %±2 %Pass
Minimum openable area, Table 6-7
11.2% of floor
ASHRAE Standard 62.1-2022
Table 6-7 (printed p28), with Table 6-1 office rates (printed p19)
11.2% of floor0.00 %exactPass
Minimum openable area, one opening
11.2 % × 24 m²
2.688m²
ASHRAE Standard 62.1-2022
Table 6-7 (printed p28), with Table 6-1 office rates (printed p19)
2.688m²0.00 %±2 %Pass

NV-12

Guide B2 Table 2.5 — maximum depth by strategy, 3 m floor to ceiling

Inputs

  • Floor-to-ceiling height 3 m, CIBSE design standard
Checks for case NV-12
QuantityExpectedSourceMEPCalcΔToleranceResult
Maximum depth, single-sided single opening
Single-sided openings: 2.5 × 3 m
7.5m
CIBSE Guide B2 2016, Ventilation and ductwork
Table 2.5 (printed p2-18)
7.5m0.00 %exactPass
Maximum depth, single-sided high + low openings
Single-sided openings: 2.5 × 3 m
7.5m
CIBSE Guide B2 2016, Ventilation and ductwork
Table 2.5 (printed p2-18)
7.5m0.00 %exactPass
Maximum depth, cross ventilation
Cross flow: 5.0 × 3 m
15m
CIBSE Guide B2 2016, Ventilation and ductwork
Table 2.5 (printed p2-18)
15m0.00 %exactPass
Maximum depth, stack ventilation
Stack ventilation: 5.0 × 3 m
15m
CIBSE Guide B2 2016, Ventilation and ductwork
Table 2.5 (printed p2-18)
15m0.00 %exactPass