VD-01
Open-plan office, 200 m² with 30 people, mixing ventilation (CIBSE)
Inputs
- Open-plan office, 200 m², 2.7 m high, 30 people
- Mixing ventilation, high-level supply cooler than the room
| Quantity | Expected | Source | MEPCalc | Δ | Tolerance | Result |
|---|---|---|---|---|---|---|
Outdoor air required 10 L/s per person × 30 = 300 l/s. The Approved Document F Vol 2 §1.32 area leg, 1 L/s·m² × 200 = 200 l/s, is lower. | 300l/s | CIBSE Guide A 2015, Environmental design Table 1.5, offices (held copy p71) | 300l/s | 0.00 % | ±2 % | Pass |
Supply air after ventilation effectiveness Mixing, high-level supply, supply cooler than the room: Ev 0.9 to 1.0. The calculation takes the lower 0.9: 300 ÷ 0.9 = 333.3 l/s. | 333.33l/s | CIBSE Guide A 2015, Environmental design Table 1.11 (held copy p101) | 333.33l/s | 0.00 % | ±2 % | Pass |